DATA CENTRES (SUSTAINABILITY REPORTING OBLIGATIONS) REGULATIONS
Table of Provisions (13)
Statutory Text (13 Articles)
OBLIGATIONS)
SUBSIDIARY LEGISLATION 545.42
DATA CENTRES (SUSTAINABILITY REPORTING
OBLIGATIONS) REGULATIONS
28th November, 2025
LEGAL NOTICE 271 of 2025.
(1)
The title of these regulations is the Data Centres
(Sustainability Reporting Obligations) Regulations.
(2)
The scope of these regulations is to transpose Article 12
and Article 26(6) of Directive (EU) 2023/1791 of the European
Parliament and of the Council of 13 September 2023 on energy
efficiency and amending Regulation (EU) 2023/955 (recast).
(regulation 3)
Part A
Minimum requirements for Monitoring and Publishing the Energy
Performance of Data Centres
The following minimum information shall be monitored and
published with regard to the energy performance of data centres
referred to in regulation 3
(a)
the name of the data centre, the name of the owner
and operators of the data centre, the date on which the data
centre started its operations and the locality where the data
centre is based;
(b)
the floor area of the data centre, the installed
OBLIGATIONS)
power, the annual incoming and outgoing data traffic, and the
amount of data stored and processed within the data centre;
(c)
the performance, during the last full calendar year,
of the data centre in accordance with key performance indicators
about, inter alia, energy consumption, power utilisation,
temperature set points, waste heat utilisation, water usage and
use of renewable energy.
OBLIGATIONS)
Part B
Data Centre General Information
Name of the Data
Centre
Data
Centre
Owner(s)
Data
Centre
Operator(s) (if different
from owner(s))
Date on which the
Data Centre commenced
operations
Locality of the
Data Centre
Data Specific to the Reporting Period
Reporting Period
Start Date
Reporting Period
End Date
Data Centre floor
area
Installed Power
Annual
Data
Traffic - Incoming
Annual
Data
Traffic - Outgoing
Amount of Data
Stored within Data Centre
Amount of Data
Processed within Data
Centre
Energy
Consumption
Power Utilisation
Temperature
Set
Points
Waste
Heat
Utilisation
Water
Consumption
Renewable Energy
used
OBLIGATIONS)
Information which is subject to European Union and Maltese
laws protecting trade and business secrets and confidentiality shall not
be made publicly available by the data centre. This information shall be
marked as confidential in any submissions made in satisfaction of the
obligations in accordance with these regulations.
(1)
In these regulations, unless the context otherwise
requires
"Act" means the Regulator for Energy and Water
Services Act;
"co-hosting customer" means a physical or legal person
who obtains access to a network or networks, servers, and
storage equipment in a co-hosting data centre on which they
operate their own services and applications;
"co-hosting data centre" means a data centre in which
one (1) or more customers are provided with access to network
or networks, servers, and storage equipment on which they
operate their own services and applications and where both the
information technology equipment and the support
infrastructure of the building are provided as a service by the
data centre operator;
"co-hosting data centre operator" means a physical or
legal person who manages the co-hosting data centre space,
security, network access, power, cooling, network or networks,
servers, and storage equipment, and part of the necessary
software to deliver information technology services to one (1)
or more customers, including information technology
outsourcing;
"colocation customer" means a physical or legal person
who owns and manages one (1) or more networks, servers and
storage equipment located in a colocation data centre in which
they purchase managed space, power, and cooling capacity;
"colocation data centre" means a data centre in which one
(1) or more customers install and manage their own network or
OBLIGATIONS)
networks, servers and storage equipment and services;
"colocation data centre operator" means a physical or
legal person who manages and sells space, security, network
access, power and cooling capacity in the entire colocation data
centre to one (1) or more customers who install and manage their
own network or networks, servers and storage equipment and
services;
"Commission" means the European Commission;
"Commission Delegated Regulation" means the
Commission Delegated Regulation (EU) 2024/1364 of 14 March
2024 on the first phase of the establishment of a common Union
rating scheme for data centres adopted in accordance with
Article 33(3) of the Directive;
"data centre" means a structure or a group of structures
used to house, connect and operate computer systems and, or
servers and associated equipment for data storage, processing
and, or distribution, as well as related activities;
"data centre computer room floor area" means the total
floor area within the data centre that accommodates the data
processing, data storage and telecommunication equipment that
provide the information technology services of the data centre;
"data centre operator" means enterprise data centre
operator, colocation data centre operator or co-hosting data
centre operator;
"data centre total floor area" means the total floor area of
all floors of the structure or group of structures that constitute
the data centre;
"Directive" means Directive (EU) 2023/1791 of the
European Parliament and of the Council of 13 September 2023
on energy efficiency and amending Regulation (EU) 2023/955
(recast);
"enterprise data centre" means a data centre that is
operated by an enterprise, and of which the sole purpose is to
deliver and manage the information technology needs of the
enterprise;
"enterprise data centre operator" means a physical or legal
person who manages the entire enterprise data centre, including
the building and the use of the information technology services
delivered;
"European Database on data centres" means the database
OBLIGATIONS)
established by the European Commission in accordance with
Article 12(3) of the Directive, which is intended for the
collection of information to be communicated by obligated data
centres in conformity with any delegated Act adopted by the
Commission in accordance with Article 33(3) of the Directive;
"installed information technology power demand" means
the sum of the nominal power demand, in kW, of the network or
networks, servers and storage equipment installed in the data
centre computer room floor area;
"Malta" shall have the same meaning as assigned to it in
article 124 of the Constitution of Malta;
"obligated data centres" means all data centres located in
Malta, including co-hosting data centres, colocation data
centres and enterprise data centres, having an installed
information technology power demand of at least five hundred
kilowatts (500kW).
(2)
Unless the context otherwise requires, words and
phrases used in these regulations which are not defined in this
regulation shall have the same meaning as assigned to them in
the Energy Efficiency Regulations.
(regulation 6)
Part A
Cost-Benefit Analysis
Cost-benefit analysis shall provide information for the purpose
of the measures referred to in regulation 6 as follows
1. If an installation without heat recovery is planned, a
comparison shall be made between the planned installation or the
planned refurbishment and an equivalent installation producing the
same amount of process heat, but recovering the waste heat and
supplying heat through a district heating and cooling network.
2. Within a defined geographical boundary, the assessment
shall take into account the planned installation and any appropriate
existing or potential heat or cooling demand points that may be
supplied from it, taking into account rational possibilities, for example,
technical feasibility and distance.
3. The system boundary shall be set to include the planned
installation and the heat and cooling loads, such as buildings and
industrial process. Within this system boundary the total cost of
providing heat shall be determined for both cases and compared.
4. Heat or cooling loads shall include existing heat or
cooling loads, such as an industrial installation or an existing district
heating or cooling system and also in urban areas, the heat or cooling
load and costs that would exist if a group of buildings or part of a city
were provided with or connected into a new district heating or cooling
network, or both.
5. Cost-benefit analysis shall be based on a description of
the planned installation and the comparison installations and shall
cover thermal capacity, planned usage and the number of planned
operating hours every year, location and thermal demand.
6. An assessment of waste heat utilisation shall take into
consideration current technologies. The assessment shall take into
consideration the direct use of waste heat or its upgrading to higher
temperature levels, or both. In the case of waste heat recovery on-site,
at least the use of heat exchangers, heat pumps, and heat to power
technologies shall be assessed. In the case of waste heat recovery off-
OBLIGATIONS)
site, at least industrial installations, agriculture sites and district
heating networks shall be assessed as potential demand points.
7. For the purpose of the comparison, the thermal energy
demand and the types of heating and cooling used by the nearby heat
or cooling demand points shall be taken into account. The comparison
shall cover infrastructure related costs for the planned and comparison
installation.
8. Cost-benefit analysis for the purposes of regulation 6
shall include an economic analysis covering a financial analysis
reflecting actual cash flow transactions from investing in, and the
operating of, individual installations.
9. Projects with positive cost-benefit outcome are those
where the sum of discounted benefits in the economic and financial
analysis exceeds the sum of discounted costs (cost-benefit surplus).
10. The cost-benefit analysis shall be carried out in line with
any further guiding principles which may be published for this purpose
in relation to the methodology, assumptions and timelines for the
economic analysis.
Part B
Information to be supplied within six (6) months of the completion of
the cost-benefit analysis
1. Data on the amount of available heat supply and heat
parameters.
2. Number of planned operating hours every year.
3. Geographical location of the site.
(1)
Owners and operators of obligated data centres
shall, by the 15th May of every year, make publicly available the
information set out in the First Schedule.
(2)
The reporting obligation referred to in sub-regulation (1)
shall not apply to those data centres used for, or which provide their
services exclusively with the final aim of defence and civil protection.
(3)
The obligation referred to in sub-regulation (1) shall be
satisfied through the publishing of the form available in Part B of the
First Schedule.
(1)
Operators of obligated data centres shall monitor
and communicate to the European database on data centres any
information and key performance indicators required by the
Commission Delegated Regulation, and any other delegated act
adopted by the Commission in accordance with Article 33(3) of the
Directive.
(2)
Operators of obligated data centres shall, by the 15th
May of each year, communicate to the European database with regard
to the obligations of data centres described.
Data centre operators shall put in place any arrangements
which may be necessary for the obtaining of information from
customers or third parties, including with colocation data centre
OBLIGATIONS)
customers and co-hosting data centre customers, as the case may be,
which are required to ensure timely compliance with the obligations
referred to in regulations 3 and 4.
(1)
Data centre operators with a total rated energy
input exceeding one megawatt (1MW) shall, following the 11th
October 2025, utilise the waste heat or other waste heat recovery
applications, unless they can demonstrate that it is not technically or
economically feasible in accordance with the assessment referred to in
sub-regulation (2).
(2)
Data centres operators shall carry out an installation level
cost-benefit analysis in accordance with Part A of the Second Schedule
in order to assess, at a minimum, technical feasibility, cost-efficiency
and the impact on energy efficiency and local heat demand, including
seasonal variation, of utilising waste heat to satisfy economically
justified demand, and of the connection of such installation to a district
heating network or to an efficient or renewable energy source-based
district cooling system, or other waste heat recovery applications.
(3)
The analysis referred to in sub-regulation (2) shall be
carried out whenever a data centre with a total rated energy input
exceeding one megawatt (1MW) is newly planned or substantially
refurbished and shall consider cooling system solutions that allow
removing or capturing the waste heat at useful temperature level with
minimal ancillary energy inputs.
(4)
Within six (6) months of the conclusion of a cost-benefit
analysis carried out in accordance with sub-regulation (2), the data
centre operator or the developer, as the case may be, shall communicate
the information listed in Part B of the Second Schedule to the
Regulator.
(5)
Any data centres whose waste heat is used or shall be
used in a district heating network or directly for space heating,
domestic hot water preparation or other uses in the building or group of
buildings or facilities where it is located shall be exempt from the
application of this regulation
Provided that such exemption may be subject to
thresholds set by the Regulator, expressed in terms of the amount of
available useful waste heat.
The obligations arising from regulations 3(1), 4(1) and 5
are not intended to replace, and shall be without prejudice to any other
obligations which may be applicable to data centres as they may arise
out of any other law such as obligations in relation to the
implementation of an energy management system, the drawing up of an
action plan based upon the recommendations emanating from
obligatory energy audits, and the publication thereof in the annual
OBLIGATIONS)
report of the enterprise having any obligations in accordance with
these obligations.
(1)
The Regulator may impose an administrative
penalty upon any person who breaches any provision of these
regulations or who fails to comply with any directive or decision given
by the Regulator in ensuring compliance with these regulations.
(2)
An administrative penalty imposed in accordance with
sub-regulation (1) shall not exceed five thousand euro (€5,000) for
each breach.
For the purposes of an appeal in respect of a decision
of the Regulator and an administrative penalty, Part VI of the Act
shall apply mutatis mutandis.
Any person who
(a)
wilfully or through negligence acts in breach of
any provision of these regulations;
(b)
fails to comply with any lawful order in relation to
these regulations; or
(c)
makes a declaration or submits information for
any purpose of these regulations which is false, misleading or
incorrect in any material respect,
shall be guilty of an offence against these regulations and shall
on conviction be liable to a fine (multa) of not more than ten thousand
euro (€10,000).