S.I. No. 7/1932 - Electricity Regulations, 1932.
Table of Provisions (33)
Statutory Text (33 Articles)
1. All
apparatus
and
conductors
shall be sufficient in size and power for the work they are called upon to do, and so constructed, installed, protected, worked and maintained as to prevent
danger
so far as is reasonably practicable.
2. All
conductors
shall either be
covered with insulating material
, and further efficiently protected where necessary to prevent
danger
, or they shall be so placed and safeguarded as to prevent
danger
so far as is reasonably practicable.
3. Every switch, switch-fuse, circuit-breaker, and isolating link shall be:—(
a
) so constructed, placed, or protected as to prevent
danger
; (
b
) so constructed and adjusted as accurately to make and to maintain good contact; (
c
) provided with an efficient handle or other means of working, insulated from the
system
, and so arranged that the hand cannot inadvertently touch
live
metal; (
d
) so constructed or arranged that it cannot accidentally fall or move into contact when left out of contact.
4. Every switch intended to be used for breaking a
circuit
and every circuit-breaker shall be so constructed that it cannot with proper care be left in partial contact. This applies to each pole of double-pole or multipole switches or circuit-breakers.
Every switch intended to be used for breaking a
circuit
and every circuit-breaker shall be so constructed that an arc cannot accidentally be maintained.
5. Every fuse, and every automatic circuit-breaker used instead thereof, shall be so constructed and arranged as effectively to interrupt the current before it so exceeds the working rate as to involve
danger
. It shall be of such construction or be so guarded or placed as to prevent
danger
from over-heating, or from arcing or the scattering of hot metal or other substance when it comes into operation. Every fuse shall be either of such construction or so protected by a switch that the fusible metal may be readily renewed without
danger
.
6. Every electrical joint and connection shall be of proper construction as regards conductivity, insulation, mechanical strength and protection.
7. Efficient means, suitably located, shall be provided for cutting off all
pressure
from every part of a
system
, as may be necessary to prevent
danger
.
8. Efficient means suitably located shall be provided for protecting from excess of current every part of a
system
, as may be necessary to prevent
danger
.
9. Where one of the
conductors
of a
system
is connected to earth, no single-pole switch, other than a link for testing purposes or a switch for use in controlling a generator or transformer, shall be placed in such
conductor
or any branch thereof.
A switch, or automatic or other cut-out, may, however, be placed in the connection between the
conductor
and earth at the generating station or transformer station, for use in testing and emergencies only.
10. Where one of the main
conductors
of a
system
is
bare
and uninsulated, no switch, fuse, or circuit-breaker shall be placed in that
conductor
or in any
conductor
connected thereto, and the said
conductor
shall be
earthed
.
Nevertheless, switches, fuses, or circuit-breakers may be used to break the connection with the generators or transformers supplying the power; provided that in no case of
bare conductor
the connection of the
conductor
with earth is thereby broken.
11. Every motor, converter and transformer shall be protected by efficient means suitably placed, and so connected that all
pressure
may thereby be cut off from the motor, converter or transformer as the case may be, and from all
apparatus
in connection therewith; provided, however, that where one point of the
system
is connected to earth, there shall be no obligation to disconnect on that side of the
system
which is connected to earth.
12. Every electrical motor shall be controlled by an efficient switch or switches for starting and stopping, so placed as to be easily worked by the person in charge of the motor.
In every place in which machines are being driven by any electric motor, there shall be means at hand for either switching off the motor or stopping the machines if necessary to prevent
danger
.
13. Every flexible wire for portable
apparatus
shall be connected to the
system
either by efficient permanent joints or connections, or by a properly constructed connector.
In all cases where the person handling portable
apparatus
or pendant lamps with switches, would be liable to get a shock through a conducting floor or conducting work or otherwise, if the metal work of the portable
apparatus
became charged, the metal work must be efficiently
earthed
; and any flexible metallic covering of the
conductors
shall be itself efficiently
earthed
and shall not itself be the only earth connection for the metal of the
apparatus.
And a lampholder shall not be in metallic connection with the guard or other metal work of a portable lamp.
Portable
apparatus
and its flexible wire shall be controlled by efficient means suitably located, and capable of cutting off the
pressure
, and the metal work shall be efficiently
earthed
independently of any flexible metallic cover of the
conductors
, and any such flexible covering shall itself be independently
earthed
.
14. The general arrangement of
switchboards
shall, so far as reasonably practicable, be such that—
(
a
) All parts which may have to be adjusted or handled are readily accessible.
(
b
) The course of every
conductor
may where necessary be readily traced.
(
c
)
Conductors
, not arranged for connection to the same
system
, are kept well apart, and can where necessary be readily distinguished.
(
d
) All
bare conductors
are so placed or protected as to prevent
danger
from accidental short circuit.
15. Every
switchboard
having
bare conductors
normally so exposed that they may be touched, shall, if not located in an area or areas set apart for the purposes thereof, where necessary be suitably fenced or enclosed.
No person except an
authorised person
, or a person acting under his immediate supervision, shall for the purpose of carrying out his duties have access to any part of an area so set apart.
16. All
apparatus
appertaining to a
switchboard
and requiring handling, shall so far as practicable be so placed or arranged as to be operated from the working platform of the
switchboard
, and all measuring instruments and indicators connected therewith shall, so far as practicable, be so placed as to be observed from the working platform. If such
apparatus
be worked or observed from any other place, adequate precautions shall be taken to prevent
danger
.
17. At the working platform of every
switchboard
, and in every
switchboard passage-way
, if there be
bare conductors
exposed or arranged to be exposed when
live
so that they may be touched, there shall be a clear and unobstructed passage of ample width and height, with a firm and even floor. Adequate means of access, free from
danger
shall be provided for every
switchboard
passage-way
.
The following provisions shall apply to all such
switchboard
working platforms and
passage-ways
, unless the
bare conductors
, whether overhead or at the sides of the
passage-ways
, are otherwise adequately protected against
danger
by divisions or screens or other suitable means:—
(
a
) Those constructed for
low-pressure switchboards
shall have a clear height of not less than 7 ft. and a clear width measured from
bare
conductor
of not less than 3 ft.
(
b
) Those constructed for
high-pressure switchboards
, other than operating desks or panels working solely at
low-pressure
, shall have a clear height of not less than 8 ft. and a clear width measured from
bare conductor
of not less than 3 ft. 6 in.
(
c
)
Bare conductors
shall not be exposed on both sides of the
switchboard passage-way unless either (i) clear width of the passage is in the case of low-pressure
not less than 4 ft. 6 in., and in the case of
high-pressure
not less than 8 ft., in each case measured between
bare conductors
, or (ii) the
conductors
on one side are so guarded that they cannot be accidentally touched.
18. In every
switchboard
for
high-pressure
:—
(
a
) Every
high-pressure conductor
within reach from the working platform or in any
switchboard passage-way
shall be so placed or protected as adequately to prevent
danger
.
(
b
) The metal cases of all instruments working at
high-pressure
shall be either
earthed
or completely enclosed with insulating covers.
(
c
) All metal handles of
high-pressure
switches, and, where necessary to prevent
danger
, all metal gear for working the switches, shall be
earthed
.
(
d
) When work has to be done on any
switchboard
, then, unless the
switchboard
be otherwise so arranged as to secure that the work may be carried out without
danger
, either (i) the
switchboard
shall be made
dead
, or (ii) if the said
switchboard
be so arranged that the
conductors
thereof can be made
dead
in sections, and so separated by permanent or removable divisions or screens from all adjoining sections of which the
conductors
are
live
, that work on any section may be carried out without
danger
, that section on which work has to be done shall be made
dead
.
19. All parts of generators, motors, transformers, or other similar
apparatus
, at
high-pressure
and within reach from any position in which any person employed may require to be, shall be, so far as reasonably practicable, so protected as to prevent
danger
.
20. Where a
high-pressure
supply is transformed for use at a lower
pressure
, or energy is transformed up to above
low-pressure
, suitable provision shall be made to guard against
danger
by reason of the lower-pressure
system
becoming accidentally charged above its normal
pressure
by leakage or contact from the higher-pressure
system
.
21. Where necessary to prevent
danger
, adequate precautions shall be taken either by
earthing
or by other suitable means to prevent any metal other than the
conductor
from becoming electrically charged.
22. Adequate precautions shall be taken to prevent any
conductor
or
apparatus
from being accidentally or inadvertently electrically charged when persons are working thereon.
23. Where necessary, adequately to prevent
danger
,
insulating stands
or
screens
shall be provided and kept permanently in position, and shall be maintained in sound condition.
24. Portable
insulating stands, screens, boots, gloves
, or other suitable means shall be provided and used when necessary adequately to prevent
danger
, and shall be periodically examined by an
authorised person.
25. Adequate working space and means of access, free from
danger
, shall be provided for all
apparatus
that has to be worked or attended to by any person.
26. All those parts of premises in which
apparatus
is placed shall be adequately lighted to prevent
danger
.
27. All
conductors
and
apparatus
exposed to the weather, wet, corrosion, inflammable surroundings or explosive atmosphere, or used in any process or for any special purpose other than for lighting or power, shall be so constructed or protected, and such special precautions shall be taken as may be necessary adequately to prevent
danger
in view of such exposure or use.
28. No person except an
authorised person
or a competent person acting under his immediate supervision shall undertake any work where technical knowledge or experience is required in order adequately to avoid
danger
; and no person shall work alone in any case in which
the Minister
directs that he shall not. No person except an
authorised person
, or a competent person acting under his immediate supervision, shall undertake any repair, alteration, extension, cleaning, or such work where technical knowledge or experience is required in order to avoid
danger
, and no one shall do such work unaccompanied.
Where a contractor is employed, and the
danger
to be avoided is under his control, the contractor shall appoint the
authorised person
, but if the
danger
to be avoided is under the control of the occupier, the occupier shall appoint the
authorised person.
29. Instructions in the
prescribed
form as to the treatment of persons suffering from electric shock shall be affixed in all premises where electrical energy is generated, transformed, or used.
30. Every
sub-station
shall be substantially constructed, and shall be so arranged that no person other than an
authorised person
can obtain access thereto otherwise than by the proper entrance, or can interfere with the
apparatus
or
conductors
therein from outside: and shall be provided with efficient means of ventilation and be kept dry.
31. Every
sub-station
shall be under the control of an
authorised person
, and none but an authorised person or a person acting under his immediate supervision shall enter any part thereof where there may be
danger
.
32. Every underground
sub-station
not otherwise easily and safely accessible shall be provided with adequate means of access by a door or trap-door, with a staircase or ladder securely fixed and so placed that no
live
part of any
switchboard
or any
bare conductor
shall be within reach of a person thereon: Provided, however, that the means of access to such
sub-station
shall be a doorway and staircase (
a
) if any person is regularly employed therein, otherwise than for inspection or cleaning, or (
b
) if the
sub-station
is not of ample dimensions and there is therein moving machinery other than ventilating fans.
BAILE ATHA CLIATH.
P. McGILLIGAN,
10adh Feabhra, 1932.
Aire um Thionnscail agus Thráchtála
(Minister for Industry and Commerce).
* S. R. and O. 1908, No. 1312.
† Terms to which defined meanings are given are printed throughout in italics.
STATUTORY RULES AND ORDERS. 1932. No. 7.
ELECTRICITY REGULATIONS, 1932.
FACTORY AND WORKSHOP.
DANGEROUS AND UNHEALTHY INDUSTRIES.
THE ELECTRICITY REGULATIONS, 1932, DATED 10TH FEBRUARY, 1932, MADE BY THE MINISTER FOR INDUSTRY AND COMMERCE UNDER SECTION 79 OF THE FACTORY AND WORKSHOP ACT, 1901, FOR THE GENERATION, TRANSFORMATION, DISTRIBUTION AND USE OF ELECTRICAL ENERGY IN PREMISES UNDER THE FACTORY AND WORKSHOP ACTS, 1901 TO 1920.
In pursuance of Section 79 of the Factory and Workshop Act, 1901, I hereby make the following Regulations in respect of the Generation, Transformation, Distribution and Use of Electrical Energy and direct that they shall apply in any factory or workshop, or any place to which the provisions of Section 79 of the Factory and Workshop Act, 1901, are applied by that Act.
These Regulations shall come into force on the 1st April, 1932, except as regards such electrical installations as were not subject to the Electricity Regulations made on the 23rd December, 1908, in respect of which they shall apply as from the 1st April, 1933.
From the 1st April, 1932, the Regulations dated 23rd December, 1908,* shall be revoked.
DUTIES.
It shall be the duty of the occupier to comply with these Regulations.
And it shall be the duty of all agents, workmen, and persons employed to conduct their work in accordance with these Regulations.
DEFINITIONS.†
"
Pressure
" means the difference of electrical potential between any two
conductors
, or between a
conductor
and earth as measured by a suitable electrostatic volt-meter.
"
Low pressure
" means a
pressure
in a
system
(
a
) normally not exceeding 250 volts to earth, or
(
b
) normally not exceeding 500 volts between
conductors
in a
system
that is not
earthed
.
"
High pressure
" means a
pressure
in a
system
(
a
) normally exceeding 250 volts to earth, or
(
b
) normally exceeding 500 volts between
conductors
in a
system
that is not
earthed
.
"
System
" means an electrical system in which all the
conductors
and
apparatus
are electrically connected to a common source of electro-motive force.
"Conductor"
means an electrical conductor arranged to be electrically connected to a
system
.
"Apparatus"
means electrical apparatus, and includes all apparatus, machines, and fittings in which
conductors
are used, or of which they form a part.
"Circuit"
means an electrical circuit forming a
system
or branch of a
system
.
"Insulating stand" means a floor, platform, stand or mat.
"Insulating screen" means a screen
"Insulating boots" means boots
"Insulating gloves" means gloves
of such size, quality, and construction according to the circumstances of the use thereof, that a person is thereby adequately protected from danger.
"Covered with insulating material"
means adequately covered with insulating material of such quality and thickness that there is no
danger
.
"Bare"
means not
covered
with
insulating material
.
"Live"
means electrically charged.
"Dead"
means at, or about, zero potential, and disconnected from any
live system.
"Earthed"
means connected to the general mass of earth in such manner as will ensure at all times an immediate discharge of electrical energy without
danger
.
"Substation"
means any premises or that part of any premises in which electrical energy at
high pressure
is distributed, or in which electrical energy is transformed or converted to or from
high pressure
, except for the purpose of working instruments, relays, or similar axiliary
apparatus
.
"Switchboard"
means the collection of switches or fuses,
conductors
, and other
apparatus
in connection therewith, used for the purpose of controlling the current or
pressure
in any
system
or part of a
system
.
"Switchboard passage-way"
means any passage-way or compartment large enough for a person to enter, and used in connection with a
switchboard
when
live
.
"Authorised person"
means (
a
) the occupier, or (
b
) a contractor for the time being under contract with the occupier, or (
c
) a person employed, appointed, or selected by the occupier, or by a contractor as aforesaid, to carry out certain duties incidental to the generation, transformation, distribution, or use of electrical energy, such occupier, contractor, or person being a person who is competent for the purposes of the regulation in which the term is used.
"Danger"
means danger to health or danger to life or limb from shock, burn, or other injury to persons employed, or from fire attendant upon the generation, transformation, distribution, or use of electrical energy.
"Public supply"
means the supply of electrical energy (
a
) by any local authority, company, or person authorised by Act of the Oireachtas or Provisional Order confirmed by the Oireachtas or by licence or Order of the Electricity Supply Board to give a supply of electrical energy; or (
b
) otherwise under Electricity Supply Board Regulations.
"The Minister"
means the Minister for Industry and Commerce for the time being.
"Prescribed"
means prescribed for the time being by the Minister for Industry and Commerce.
EXEMPTIONS.